2CP5 / 2CP50 Pressure Sensor Standards


Packard electrical connector
±2.0% for roughly 100°C span
Port fitting: 1/4 SAE (7/16"–20) female flare with deflator
Internal seal: neoprene (good for most refrigerants at least to about 120°C) except 2CP5-45 which is HNBR
These are sealed gauge devices (psig = psis at sea level, psig = psia – 14.7 at sea level)


 
Sensata Part #
Production (samples)
MARS
Part #
Pressure
(with 5.00V input)
Port
Fitting
Material
Transfer function*
@ 5.00Vdc input
0.5V
4.5V
#1
"0–150"
2CP5-46
(2CP5B05 20150ANN)
33502
-14.7 psig
0 psia
0 bar
135 psig
150 psia
10.2 bar
Brass
P(psig)= 37.5*Vout–33.5
P(psia) = 37.5*Vout–18.8
P(bar) = 2.55*Vout–1.28
#2
"0–200"
2CP5-49
(2CP5B05 20200ANN)
33504
-14.7 psig
0 psia
0 bar
185 psig
200 psia
13.6 bar
Brass
P(psig)= 50.0*Vout–39.7
P(psia) = 50.0*Vout–25.0
P(bar) = 3.40*Vout–1.70
#3
"0–300"
2CP5-50
(2CP5B05 20300SNN)
33506
0 psig
14.7 psia
1 bar
300 psig
315 psia
21.4 bar
Brass
P(psig)= 75.0*Vout–37.5
P(psia) = 75.0*Vout–22.8
P(bar) = 5.10*Vout–1.55
#4
"0–400"
2CP5-51
(2CP5B05 20400SNN)
33508
0 psig
14.7 psia
1 bar
400 psig
415 psia
28.2 bar
Brass
P(psig)= 100*Vout–50.0
P(psia) = 100*Vout–35.3
P(bar) = 6.80*Vout–2.40
#5
"0–500"
2CP5-47
(2CP5B05 20500SNN)
33510
0 psig
14.7 psia
1 bar
500 psig
515 psia
35.0 bar
Brass
P(psig)= 125*Vout–62.5
P(psia) = 125*Vout–47.8
P(bar) = 8.50*Vout–3.25
 
Sensata Part #
Production (samples)
MARS
Part #
Pressure
(with 5.00V input)
Port
Fitting
Material
Transfer function*
@ 5.00Vdc input
0.5V
4.5V
#6
"0–500"
2CP5-48
(2CP5S05 20500SNN)
33512
0 psig
14.7 psia
1 bar
500 psig
515 psia
35.0 bar
Plated Steel
P(psig)= 125*Vout–62.5
P(psia) = 125*Vout–47.8
P(bar) = 8.50*Vout–3.25
#7
"0–500"
2CP5-45
 
0 psig
14.7 psia
1 bar
500 psig
515 psia
35.0 bar
Plated Steel
P(psig)= 125*Vout–62.5
P(psia) = 125*Vout–47.8
P(bar) = 8.50*Vout–3.25
#8
"0–160"
2CP5-42
(has label)
 
-14.7 psig
0 psia
0 bar
145 psig
160 psia
10.9 bar
Plated Steel
P(psig)= 39.9*Vout–34.6
P(psia) = 39.9*Vout–19.9
P(bar) = 2.71*Vout–1.36
#9
"0–510"
2CP5-43
(has label)
 
-7.5 psig
7.2 psia
.49 bar
493 psig
508 psia
34.6 bar
Plated Steel
P(psig)= 125*Vout–70.1
P(psia) = 125*Vout–55.4
P(bar) = 8.52*Vout–3.77
#10
"0–700"
2CP50-1
(has label)
 
0 psig
14.7 psia
1 bar
652 psig
667 psia
45.4 bar
Plated Steel
P(psig)= 166.8*Vout–83.6
P(psia) = 166.8*Vout–68.9
P(bar) = 11.34*Vout–4.69

* Transfer functions for both HPT and PT above are based on 5.00Vdc input
– Output is ratiometric to input. IE: if supply voltage drops 2% to 4.9V, output will drop 2%
– Thus, to maintain accuracy with less regulated power, “Vout” should be substituted with “Vout*(5/Vin)”